Gas Regulator: RTZ-FQ Series
|
|
|
|
|
|
25FQ、40FQ
50FQ
|
|
Purpose
It provides pressure adjustment in civil buildings,and also used in small or medium public locations for pressure adjustment and pressure stablization.
Applicable medium
Natural gas, Manufactured gas, Liquefied petroleum gas,and other gases.
Technical Parameters
Maximum Inlet Pressure P1max: 0.4 MPa
Inlet Pressure Ranges P1: 0.02-0.4 MPa
Outlet Pressure Ranges P2: 1-5 KPa (25FQ、40FQ、50FQ)
5-15 KPa(50FQ)
Pressure Stablization Accuracy δ: ≤±5%
Close Pressure Pb: ≤ +10%
Temperature Capabilities t: -20°-60°C
Diameters DN25、DN40、DN50
Built-in Super Pressure Shutoff Valve
Self-Powered Pneumatic Control
Shutoff Accuracy ≤±5%
Reaction Time ≤1 sec
Manual Reset
Diameters of Build-in Safety Disperse valve (Except for Liquefied petroleum gas)
12、16、20、25
Different valve dimension can meet different inlet pressure and flow requirements.
Connections
RTZ-25FQ: Inlet/Outlet whorl connect G1"
RTZ-40FQ: Inlet/Outlet whorl connect G1"
RTZ-50FQ: Inlet/Outlet flange connect DN50 PN1.6 MPa
|
|
|
25FQ , 40FQ |
|
50FQ |
|
|
Dimentions |
|
|
Size code
Model |
L |
C |
E |
E1 |
H |
H1 |
D |
25FQ |
100 |
180 |
370 |
235 |
160 |
110 |
G1" |
40FQ |
120 |
225 |
420 |
275 |
175 |
125 |
G11/2" |
50FQ |
230 |
325 |
595 |
415 |
330 |
250 |
DN50 |
|
|
|
|
|
|
25FQ
Outlet Pressure KPa |
Inlet
Pressure MPa |
0.02 |
0.03 |
0.04 |
0.05 |
0.06 |
0.07 |
0.08 |
0.1 |
0.13 |
0.15 |
0.18 |
0.2 |
0.3 |
0.4 |
1 |
4 |
6 |
9 |
13 |
13 |
13 |
14 |
14 |
15 |
16 |
19 |
20 |
25 |
26 |
2 |
10 |
13 |
17 |
18 |
19 |
21 |
22 |
24 |
26 |
28 |
31 |
33 |
29 |
30 |
3 |
12 |
15 |
18 |
20 |
22 |
24 |
26 |
30 |
34 |
37 |
42 |
41 |
38 |
40 |
4 |
12 |
15 |
18 |
20 |
22 |
24 |
26 |
30 |
34 |
37 |
42 |
48 |
46 |
46 |
5 |
11 |
15 |
18 |
20 |
22 |
24 |
26 |
30 |
34 |
37 |
42 |
46 |
51 |
52 |
|
|
|
|
|
|
40FQ
Outlet Pressure KPa |
Inlet
Pressure MPa |
0.02 |
0.03 |
0.04 |
0.05 |
0.06 |
0.07 |
0.08 |
0.1 |
0.13 |
0.15 |
0.18 |
0.2 |
0.3 |
0.4 |
1 |
6 |
6 |
6 |
6 |
10 |
16 |
20 |
24 |
25 |
27 |
30 |
35 |
50 |
50 |
2 |
19 |
22 |
30 |
35 |
38 |
41 |
44 |
45 |
50 |
65 |
80 |
85 |
85 |
90 |
3 |
21 |
26 |
30 |
34 |
38 |
41 |
44 |
50 |
57 |
62 |
70 |
75 |
100 |
125 |
4 |
20 |
26 |
30 |
34 |
38 |
41 |
44 |
50 |
57 |
62 |
70 |
75 |
100 |
125 |
5 |
19 |
25 |
30 |
34 |
38 |
41 |
44 |
50 |
57 |
62 |
70 |
75 |
100 |
125 |
|
|
|
|
|
|
50FQ
Outlet Pressure KPa |
Inlet
Pressure MPa |
0.02 |
0.03 |
0.04 |
0.05 |
0.06 |
0.07 |
0.08 |
0.1 |
0.13 |
0.15 |
0.18 |
0.2 |
0.3 |
0.4 |
2 |
23 |
29 |
34 |
38 |
42 |
45 |
49 |
55 |
63 |
68 |
77 |
82 |
110 |
137 |
3 |
23 |
29 |
33 |
38 |
42 |
45 |
48 |
55 |
63 |
68 |
77 |
82 |
110 |
137 |
5 |
14 |
21 |
26 |
30 |
41 |
45 |
48 |
55 |
63 |
68 |
77 |
82 |
110 |
137 |
8 |
15 |
20 |
25 |
30 |
41 |
45 |
48 |
54 |
63 |
68 |
77 |
82 |
110 |
137 |
10 |
14 |
19 |
25 |
30 |
40 |
44 |
48 |
54 |
63 |
68 |
77 |
82 |
110 |
137 |
12 |
12 |
18 |
24 |
29 |
40 |
44 |
48 |
54 |
63 |
68 |
77 |
82 |
110 |
137 |
15 |
- |
17 |
23 |
29 |
39 |
43 |
47 |
54 |
63 |
68 |
77 |
82 |
110 |
137 |
|
|
|